1All community and non-transient non-community systems that are susceptible to asbestos contamination (e.g., source water contaminated by asbestos or use of asbestos-cement pipe within the distribution system) shall monitor to determine compliance with the maximum contaminant level for asbestos specified in paragraph 4362-550.310(1)(a), 44F.A.C., according to the following:
49(1) Each community and non-transient non-community water system that is susceptible to asbestos contamination (e.g., source water contaminated by asbestos or use of asbestos-cement pipe within the distribution system) shall monitor for asbestos during the year prescribed by paragraph 8862-550.500(3)(e), 89F.A.C. Source waters in Florida are not considered to be susceptible to asbestos contamination. The water system shall monitor source waters when notified in writing by the Department that the system is susceptible to asbestos contamination.
125(a) A system susceptible to asbestos contamination due solely to corrosion of asbestos-cement pipe shall take one sample at a tap served by asbestos-cement pipe and under conditions where asbestos contamination is most likely to occur.
161(b) A system susceptible to asbestos contamination due solely to source water shall monitor in accordance with the provision of paragraph 18262-550.500(5)(a), 183F.A.C.
184(c) A system susceptible to contamination due both to its source water supply and corrosion of asbestos-cement pipe shall take one sample at a tap served by asbestos-cement pipe and under conditions where asbestos contamination is most likely to occur.
224(2) Reports of the result of asbestos sampling shall describe the location where the sample was taken and the reason why that location was chosen.
249(3) During the year the system is scheduled to monitor, the system shall send the Department an asbestos sampling plan, using Form 27162-555.900(10) 272detailing the location and the conditions under which the sample is to be taken.
286(4) A system without asbestos-containing components shall certify to the Department in writing, using Form 30162-555.900(10), 302that it is asbestos free. Certification shall satisfy the requirements of subsections (1), (2) and (3) above, and shall be submitted each nine-year compliance cycle during the specified year the system is required to monitor.
337(5) The Department shall reduce the monitoring frequency to annually, for systems that exceeded the maximum contaminant level for asbestos and are required to monitor quarterly as prescribed by subsection 36762-550.500(8), 368F.A.C., if the running annual average is below the maximum contaminant level. The Department shall reduce the monitoring frequency as provided in paragraph 39162-550.500(3)(d), 392F.A.C., when the average of three consecutive years of monitoring results is less than 50% of the maximum contaminant level and no sample exceeds the maximum contaminant level.
420(6) If the initial monitoring for asbestos was completed between January 1, 1990 and December 31, 1992, and the results did not exceed the maximum contaminant level specified in paragraph 45062-550.310(1)(a), 451F.A.C., the system may submit those results to the Department in lieu of monitoring during the first compliance cycle.
470(7) Compositing of samples is allowed as provided in subsection 48062-550.550(4), 481F.A.C.
482Rulemaking Authority 484403.853(3), 485403.861(9) FS. 487Law Implemented 489403.853(1), 490(3), (7), 492403.861(16), 493(17) FS. History–New 1-1-93, Amended 7-4-93, Formerly 17-550.511, Amended 9-7-94, 2-7-95, 12-9-96, 4-14-03, 11-28-04.