62-550.520. Secondary Contaminants Monitoring Requirements  


Effective on Sunday, November 28, 2004
  • 1(1) Analysis to determine compliance with Rule 862-550.320, 9F.A.C., shall be conducted by all community water systems and shall be repeated once each compliance period. Lime softening facilities may operate above 8.5 but less than or equal to 9.0 pH units without Department approval, and may operate above 9.0, but less than or equal to 10.0 pH units upon approval by the Department of a written demonstration by the water system that operating at the higher pH will not cause the treatment plant to suffer operational failures, that minimum disinfectant levels can be maintained throughout the distribution system, and that the system can remain in compliance with the lead and copper and microbiological provisions of Chapters 62-550 and 62-555, F.A.C. Surface water systems or ground water systems that are required to demonstrate the effectiveness of their primary disinfection treatment process to meet 143Giardia lamblia 145or virus inactivation requirements shall operate within a pH range as specified for their disinfectant in the tables in Appendix E of the Guidance Manual adopted in subsection 17362-555.335(1), 174F.A.C.

    175(2) If the results of an analysis indicate that the level of fluoride exceeds the secondary maximum contaminant level, the supplier of water shall notify the public pursuant to Rule 20562-560.430, 206F.A.C., and take corrective action as approved by the Department pursuant to Rule 21962-560.700, 220F.A.C.

    221(3) With the exception of pH, the system is in violation if the level of a secondary contaminant at any sampling point is greater than the secondary maximum contaminant level.

    251Rulemaking Authority 253403.861(9) FS. 255Law Implemented 257403.853(1), 258(3), 259403.861(16), 260(17) FS. History–New 11-19-87, Formerly 17-22.320, Amended 1-18-89, 5-7-90, 1-1-93, 7-4-93, Formerly 17-550.520, Amended 11-28-04.

     

Rulemaking Events:

Related Statutes: