62-555.360. Cross-Connection Control for Public Water Systems  


Effective on Monday, May 5, 2014
  • 1(1) Cross-connections, as defined in Rule 762-550.200, 8F.A.C., are prohibited 11unless appropriate backflow protection is provided to prevent backflow through the cross-connection into the public water system. This does not prohibit a public water system from being interconnected to another public water system of the same type without backflow protection (i.e., a community water system [CWS] may be interconnected to another CWS without backflow protection, a non-transient non-community water system [NTNCWS] may be interconnected to another NTNCWS without backflow protection, and a transient non-community water system [TWS] may be interconnected to another TWS without backflow protection).

    97(a) Appropriate backflow protection for various applications is described in 107Recommended Practice for Backflow Prevention and Cross-Connection Control: AWWA Manual M14, 118Third Edition, as clarified and modified in paragraphs (b) and (c) below and in Table 62-555.360-2, which appears at the end of this section. The third edition of 146AWWA Manual M14 149is incorporated herein by reference; is available from the American Water Works Association, 6666 West Quincy Avenue, Denver, CO 80235, www.awwa.org; and is available for review at the Department of Environmental Protection, Source and Drinking Water Program, MS 3520, 2600 Blair Stone Road, Tallahassee, Florida 32399-2400, at the Department of Environmental Protection district offices, and at the Approved County Health Departments.

    210(b) Except for the temporary cross-connections described in paragraph (c) below, cross-connections between a public water system and a wastewater system or reclaimed water system are prohibited (i.e., an air gap shall be maintained between any public water system and any wastewater system or reclaimed water system). The Department shall allow an exception to this requirement if the supplier of water provides justification for the exception and provides alternative backflow protection that achieves a level of reliability and public health protection similar to that achieved by an air gap (e.g., two biannually-tested reduced-pressure principle assemblies installed in series); however, in no case shall the Department allow a single, annually-tested mechanical backflow preventer to be used as the only protection against backflow of wastewater or reclaimed water into a public water system.

    341(c) Temporary cross-connections may be made between a public water system and a wastewater system or reclaimed water system for either of the following purposes:

    3661. To supply water for flushing or testing a new wastewater force main or new reclaimed water main, in which case a double check valve assembly or reduced-pressure principle assembly shall be provided at the cross-connection.

    4022. To supply water for temporarily operating a new reclaimed water main that has not yet been connected to a reclaimed water supply, in which case a reduced-pressure principle assembly shall be provided at the cross-connection.

    438(2) Each community water system (CWS) shall establish and implement a cross-connection control program 452utilizing backflow protection at or for service connections from the CWS in order to protect the CWS from contamination caused by cross-connections on customers’ premises477. This program shall include a written plan that is developed using recommended practices of the American Water Works Association set forth in 500Recommended Practice for Backflow Prevention and Cross-Connection Control508: AWWA Manual M14, 512Third Edition, as clarified and modified in paragraph (a) below. The third edition of 526AWWA Manual M14 529is incorporated herein by reference and is available as indicated in paragraph 54162-555.360(1)(a), 542F.A.C.

    543(a) The minimum components that each CWS shall include in its written cross-connection control plan are listed and described in Table 62-555.360-1, which appears at the end of this section. The categories of customers for which each CWS shall ensure backflow protection is provided at or for the service connection from the CWS to the customer are listed in Table 62-555.360-2, which appears at the end of this section.

    612(b) Each CWS serving more than 10,000 persons shall prepare and submit cross-connection control program annual reports. The first annual report shall cover calendar year 2016, and subsequent annual reports shall cover each calendar year thereafter. These reports shall be prepared using Form 65662-555.900(13), 657Cross-Connection Control Program Annual Report, effective 5-5-14, which is incorporated herein by reference and which is available as described in Rule 67862-555.900, 679F.A.C., and at 682http://www.flrules.org/683G684ateway/reference.asp?685N686o=Ref-04104687. These reports shall be submitted to the appropriate Department of Environmental Protection district office or Approved County Health Department within three months after the end of the calendar year covered by the report.

    721(3) Upon discovery of a prohibited 727or inappropriately protected 730cross-connection, public water systems either 735shall ensure that 738the cross-connection 740is eliminated, shall ensure that 745appropriate backflow 747protection is installed to prevent backflow into the public water system, 758or shall discontinue water service. 763If the discovered cross-connection is on the premises of a customer of a community water system (CWS) and if the customer’s premises is in a category described in Table 62-555.360-2, which appears at the end of this section, the CWS shall ensure that appropriate backflow protection is provided at or for the water service connection to the customer regardless of whether the cross-connection is eliminated or whether internal backflow protection is installed at the cross-connection to the customer’s plumbing system.

    843Table 62-555.360-1: Minimum Components that Each Community Water System (CWS) Shall Include in Its Written Cross-Connection Control (CCC) Plan (Effective 5-5-14)

    864Component Number and Description

    868I. Legal authority for the CWS’s CCC program 876877i.e., an ordinance, a bylaw or resolution, or water service rules and regulations. The legal authority shall include or reference Components 2 and 3 below.

    902II. The CWS’s policy establishing where backflow protection at or for service connections from the CWS is mandatory.

    920A. This policy shall identify categories of customers for which the CWS is requiring backflow protection at or for the service connection to the customer and shall specify the minimum backflow protection that the CWS is requiring for each such category of customers.

    963B. This policy shall be no less stringent than Table 62-555.360-2, which appears at the end of Rule 98162-555.360, 982F.A.C.

    983III. The CWS’s policy regarding ownership, installation, inspection/testing, and maintenance of backflow protection that the CWS is requiring at or for service connections from the CWS.

    1009A. This policy shall specify whether the CWS or customer is responsible for installation, inspection/testing, and maintenance of backflow protection being required at or for service connections.

    1036B. This policy shall specify design and performance standards, and shall specify installation criteria, for new backflow protection being required at or for service connections. Installation criteria shall be consistent with installation criteria in 1070AWWA Manual M14 1073as incorporated into subsection 107762-555.360(2), 1078F.A.C., and shall assure the backflow protection is installed as close as practical to the CWS’s meter or customer’s property line but, in all cases, before the first distribution line off of the customer’s water service line.

    1115C. This policy shall specify the frequency for inspecting air gaps (AGs) being required at or for service connections and shall specify qualifications for persons inspecting such AGs. All AGs being required at or for service connections pursuant to Table 62-555.360-2, which appears at the end of Rule 116362-555.360, 1164F.A.C., shall be inspected at least annually.

    1171D. This policy shall specify the frequency for testing backflow preventer assemblies11831 1184being required at or for service connections, shall specify qualifications for persons testing such assemblies, and shall specify test procedures for such assemblies. Assemblies being required at or for non-residential service connections12162 1217pursuant to Table 62-555.360-2, which appears at the end of Rule 122862-555.360, 1229F.A.C., shall be tested after installation or repair and at least annually thereafter and shall be repaired if they fail to meet performance standards. Assemblies being required at or for residential service connections12622 1263pursuant to Table 62-555.360-2 shall be tested after installation or repair and at least biennially thereafter and shall be repaired if they fail to meet performance standards.

    1290E. This policy shall specify the frequency for refurbishing or replacing dual check devices (DuCs) being required at or for service connections. DuCs being required at or for service connections pursuant to Table 62-555.360-2, which appears at the end of Rule 133162-555.360, 1332F.A.C., shall be refurbished or replaced at least once every 5 to 10 years or at a lesser frequency determined by the CWS if the CWS documents that the lesser frequency is appropriate based on data from spot-testing DuCs in its system or based on data from backflow sensing meters in its system.

    1385IV. The CWS’s procedures for evaluating customers’ premises to establish the category of customer and the backflow protection being required at or for the service connection(s) from the CWS to the customer.14173

    1418A. The CWS shall evaluate the customer’s premises at a newly constructed service connection before the CWS begins supplying water to the service connection.

    1442B. The CWS shall evaluate the customer’s premises at an existing 14531454i.e., previously constructed 14571458service connection whenever the customer connects to a reclaimed water distribution system, whenever an auxiliary water system is discovered on the customer’s premises, whenever a prohibited or inappropriately protected cross-connection is discovered on the customer’s premises, and whenever the customer’s premises is altered under a building permit in a manner that could change the backflow protection required at or for a service connection to the customer.

    1524V. The CWS’s procedures for maintaining CCC program records.15334

    1534A. The CWS shall maintain a current inventory of backflow protection being required at or for service connections from the CWS.

    1555B. The CWS shall maintain records of the installation, inspection/testing, and repair of backflow protection being required at or for service connections from the CWS.

    15801 1581Backflow preventer assemblies include the following: double check valve assemblies (DCs) and double check detector assemblies (DCDAs); pressure vacuum breaker assemblies (PVBs); and reduced-pressure principle assemblies (RPs) and reduced-pressure principle detector assemblies (RPDAs).

    16142 1615For the purpose of this table, “residential service connection” means any service connection, including any dedicated irrigation or fire service connection, that is two inches or less in diameter and that supplies water to a building, or premises, containing only dwelling units; and “non-residential service connection” means any other service connection.

    16663 1667CWSs may evaluate customers’ premises using questionnaires, reviews of construction plans or pertinent records, on-site inspections, or any combination thereof.

    16874 1688CWSs may maintain all records in either electronic or paper format.

     

    1699Table 62-555.360-2: Categories of Customers for Which Each Community Water System (CWS) Shall Ensure Minimum Backflow Protection Is Provided at or for the Service Connection from the CWS to the Customer (Effective 5-5-14)

    1732Category of Customer

    1735Minimum Backflow Protection17381 1739to Be Provided at or for the Service Connection from the CWS to the Customer

    1754Beverage processing plant, including any brewery

    1760DC if the plant presents a low hazard17682; 1769or RP if the plant presents a high hazard17782

    1779Cannery, packing house, rendering plant, or any facility where fruit, vegetable, or animal matter is processed, excluding any premises where there is only restaurant or food service facility

    1807RP

    1808Car wash

    1810RP

    1811Chemical plant or facility using water in the manufacturing, processing, compounding, or treatment of chemicals, including any facility where a chemical that does not meet the requirements in paragraph 184062-555.320(3)(a), 1841F.A.C., is used as an additive to the water

    1850RP

    1851Dairy, creamery, ice cream plant, cold-storage plant, or ice manufacturing plant

    1862RP18633

    1864Dye plant

    1866RP

    1867Film laboratory or processing facility or film manufacturing plant, excluding any small, noncommercial darkroom facility

    1882RP

    1883Hospital; medical research center; sanitarium; autopsy facility; medical, dental, or veterinary clinic where surgery is performed; or plasma center

    1902RP

    1903Laboratory, excluding any laboratory at an elementary, middle, or high school

    1914RP

    1915Laundry (commercial), excluding any self-service laundry or Laundromat

    1923RP

    1924Marine repair facility, marine cargo handling facility, or boat moorage

    1934RP

    1935Metal manufacturing, cleaning, processing, or fabricating facility using water in any of its operations or processes, including any aircraft or automotive manufacturing plant

    1958DC if the facility presents a low hazard19662; 1967or RP if the facility presents a high hazard19762

    1977Mortuary

    1978RP

    1979Premises where oil or gas is produced, developed, processed, blended, stored, refined, or transmitted in a pipeline or where oil or gas tanks are repaired or tested, excluding any premises where there is only a fuel dispensing facility

    2017RP

    2018Premises where there is an auxiliary or reclaimed water system20284,5

    2030A. At or for a residential service connection203862039: DuC20417

    2042B. At or for a non-residential service connection205062051: DC if the auxiliary or reclaimed water is a low hazard20638,9; 2065or RP if the auxiliary or reclaimed water is a high hazard20778,9

    2079Premises where there is a cooling tower

    2086RP

    2087Premises where there is an irrigation system that is using potable water and that…

    2101I. Is connected directly to the CWS’s distribution system via a dedicated irrigation service connection

     

     

     

     

    2116II. Is connected internally to the customer’s plumbing system

     

    2125I. At or for a residential or non-residential dedicated irrigation service connection213762138: PVB if backpressure cannot develop in the downstream piping214810; 2149or RP if backpressure could develop in the downstream piping215910

    2160II. None216211

    2163Premises where there is a wet-pipe sprinkler, or wet standpipe, fire protection system that is using potable water and that…

    2183I. Is connected directly to the CWS’s distribution system via a dedicated fire service connection219812

     

     

     

     

     

     

     

     

     

     

     

     

     

     

     

    2199II. Is connected internally to the customer’s plumbing system

     

     

     

    2208I.A. At or for a residential dedicated fire service connection221862219: DuC if the fire protection system contains no chemical additives and is not connected to an auxiliary water system22394; 2240or RP or RPDA if the fire protection system contains chemical additives or is connected to an auxiliary water system22604,13

    2262I.B. At or for a non-residential dedicated fire service connection227262273: DC or DCDA if the fire protection system contains no chemical additives and is not connected to an auxiliary water system22954; 2296or RP or RPDA if the fire protection system contains chemical additives or is connected to an auxiliary water system23164,13

    2318II. None232011

    2321Radioactive material processing or handling facility or nuclear reactor

    2330RP

    2331Paper products plant using a wet process

    2338RP

    2339Plating facility, including any aircraft or automotive manufacturing plant

    2348RP

    2349Restricted-access facility

    2351RP

    2352Steam boiler plant

    2355RP

    2356Tall building 2358‒ i.e., a building with five or more floors at or above ground level

    2372DC if the customer has no potable water distribution lines connected to the suction side of a booster pump; or RP if the customer has one or more potable water distribution lines connect2405ed to the suction side of a booster pump

    2414Wastewater treatment plant or wastewater pumping station

    2421RP

    2422Customer supplied with potable water via a temporary or permanent service connection from a CWS fire hydrant

    2439Varies244014

    24411 2442Means of backflow protection, listed in an increasing level of protection, include the following: a dual check device (DuC); a double check valve assembly (DC) or double check detector assembly (DCDA); a pressure vacuum breaker assembly (PVB); a reduced-pressure principle assembly (RP) or reduced-pressure principle detector assembly (RPDA); and an air gap. A PVB may not be used if backpressure could develop in the downstream piping.

    25082 2509The CWS shall determine the degree of hazard. “Low hazard” or “non-health hazard” and “high hazard” or “health hazard” are defined in 2531AWWA Manual M14 2534as incorporated in paragraph 253862-555.360(1)(a), 2539F.A.C., and subsection 254262-555.360(2), 2543F.A.C.

    25443 2545A DC may be provided if it was installed before 5-5-14; and if such a DC is replaced on or after 5-5-14, it may be replaced with another DC.

    25744 2575For the purpose of this table, “auxiliary water system” means a pressurized system of piping and appurtenances using auxiliary water, which is water other than the potable water being supplied by the CWS and which includes water from any natural source such as a well, pond, lake, spring, stream, river, etc., includes reclaimed water, and includes other used water or industrial fluids described in 2639AWWA Manual M14 2642as incorporated in paragraph 264662-555.360(1)(a), 2647F.A.C., and subsection 265062-555.360(2), 2651F.A.C.; however, “auxiliary water system” specifically excludes any water recirculation or treatment system for a swimming pool, hot tub, 2670or spa. (Note that reclaimed water is a specific type of auxiliary water and a reclaimed water system is a specific type of auxiliary water system.)

    26965 2697The Department shall allow an exception to the requirement for backflow protection at or for a residential or non-residential service connection from a CWS to premises where there is an auxiliary or reclaimed water system if all of the following conditions are met:

    27406 2741For the purpose of this table, “residential service connection” means any service connection, including any dedicated irrigation or fire service connection, that is two inches or less in diameter and that supplies water to a building, or premises, containing only dwelling units; and “non-residential service connection” means any other service connection.

    27927 2793A DuC may be provided only if there is no known cross-connection between the plumbing system and the auxiliary or reclaimed water system on the customer’s premises. Upon discovery of any cross-connection between the plumbing system and any reclaimed water system on the customer’s premises, the CWS shall ensure that the cross-connection is eliminated. Upon discovery of any cross-connection between the plumbing system and any auxiliary water system other than a reclaimed water system on the customer’s premises, the CWS shall ensure that the cross-connection is eliminated or shall ensure that the backflow protection provided at or for the service connection is equal to that required at or for a non-residential service connection.

    29068 2907Reclaimed water regulated under Part III of Chapter 62-610, F.A.C., is a low hazard unless it is stored with surface water in a pond that is part of a stormwater management system, in which case it is a high hazard; well water is a low hazard unless determined otherwise by the CWS; industrial fluids and used water other than reclaimed water are high hazards unless determined otherwise by the CWS; reclaimed water not regulated under Part III of Chapter 62-610, F.A.C., and surface water are high hazards.

    29949 2995Upon discovery of any cross-connection between the plumbing system and any reclaimed water system on the customer’s premises, the CWS shall ensure that the cross-connection is eliminated.

    302210 3023A DC may be provided if both of the following conditions are met:

    303611 3037The CWS may rely on the internal backflow protection required under the 3049Florida Building Code 3052or the predecessor State plumbing code. The CWS may, but is not required to, ensure that such internal backflow protection is inspected/tested and maintained the same as backflow protection provided at or for service connections from the CWS.

    309012 3091The Department shall allow an exception to the requirement for backflow protection at or for a residential or non-residential dedicated fire service connection from a CWS to a wet-pipe sprinkler, or wet standpipe, fire protection system if both of the following conditions are met:

    313513 3136Upon discovery of any cross-connection between the fire protection system and any reclaimed water system on the customer’s premises, the CWS shall ensure that the cross-connection is eliminated.

    316414 3165The CWS shall ensure that backflow protection commensurate with the degree of hazard is provided at or for the service connection from its fire hydrant.

    3190Rulemaking Authority 3192403.086(8), 3193403.853(3), 3194403.861(9) FS. 3196Law Implemented 3198403.086(8), 3199403.852(12), 3200403.853(1), 3201403.855(3), 3202403.861(17) FS. 3204History–New 11-19-87, Formerly 17-22.660, Amended 1-18-89, 1-3-91, 1-1-93, Formerly 17-555.360, Amended 8-28-03, 5-5-14.

     

Rulemaking Events:

Historical Versions(1)

Select effective date to view different version.

Reference Materials (1)