61-30.803. Standards of Practice, Electrical Systems  


Effective on Tuesday, October 22, 2013
  • 1(1) Electrical systems and components include the following:

    9(a) Service entrance conductors, drip loop, cables, and raceways;

    18(b) Main service equipment and main disconnects;

    25(c) Service grounding;

    28(d) Interior components of main service panels and sub panels;

    38(e) Conductors;

    40(f) Over current protection devices;

    45(g) Readily accessible installed lighting fixtures, switches, and receptacles;

    54(h) Ground fault circuit interrupters;

    59(i) Amperage and voltage rating of electrical service;

    67(j) Main disconnect(s);

    70(k) Methods or types of wiring;

    76(l) Smoke detectors;

    79(m) Carbon monoxide detectors;

    83(n) Arc fault circuit interrupters.

    88(2) The inspector shall inspect all of the visible and readily accessible electrical systems and components.

    104(3) The inspector is not required to inspect:

    112(a) Remote control devices;

    116(b) Security alarm systems and components;

    122(c) Low voltage wiring, systems and components, ancillary wiring and systems and components not a part of the primary electrical power distribution system;

    145(d) Generators, photovoltaic solar collectors or battery or electrical storage devices and associated equipment.

    159(4) The inspector is not required to:

    166(a) Measure amperage, voltage or impedance;

    172(b) Perform a load calculation;

    177(c) Insert any tool, probe, or device into any electrical component;

    188(d) Determine the accuracy of circuit labeling.

    195Rulemaking Authority 197468.8325 FS. 199Law Implemented 201468.8323, 202468.832(1)(j) FS. 204History205‒New 10-22-13.

     

Rulemaking Events: