25-30.055. Systems with a Capacity or Proposed Capacity to Serve 100 or Fewer Persons  


Effective on Monday, November 10, 1986
  • 1(1) A water or wastewater system is exempt under Section 11367.022(6), F.S., 13if its current or proposed water or wastewater treatment facilities and distribution or collection system have and will have a capacity, excluding fire flow capacity, of no greater than 10,000 gallons per day or if the entire system is designed to serve no greater than 40 equivalent residential connections (ERCs). For purposes of this rule only, one ERC equals 250 gallons per day.

    77(a) Unless the Commission determines that valid local statistical data should be used, ERCs for residential use are as follows:

    97Single family detached dwellings

    1011 ERC per unit

    105Multiple family dwellings

    108.8 ERC per unit

    112Mobile homes

    114.8 ERC per unit

    118(b) ERCs for nonresidential use shall be based on meter size and type as follows:

    1331. For Water Systems

    137Meter Size

    139Meter Type

    141ERCs

    1425/8''

    143Displacement

    1441.0

    1453/4''

    146Displacement

    1471.5

    1481''

    149Displacement

    1502.5

    15111/2''

    152Displacement or Turbine

    1555.0

    1562''

    157Displacement, Compound or Turbine

    1618.0

    1623''

    163Displacement

    16415.0

    1653''

    166Compound

    16716.0

    1683''

    169Turbine

    17017.5

    1714v

    172Displacement or Compound

    17525.0

    1764''

    177Turbine

    17830.0

    1796''

    180Displacement or Compound

    18350.0

    1846v

    185Turbine

    18662.5

    1878''

    188Compound

    18980.0

    1908''

    191Turbine

    19290.0

    19310''

    194Compound

    195115.0

    19610''

    197Turbine

    198145.0

    19912''

    200Turbine

    201215.0

    2022. For Wastewater Systems

    206Meter Size

    208Meter Type

    210ERCs

    2115/8''

    212Displacement

    2131.0

    2143/4''

    215Displacement

    2161.5

    2171''

    218Displacement

    2192.5

    22011/2''

    221Displacement or Turbine

    2245.0

    2252''

    226Displacement, Compound or Turbine

    2308.0

    2313''

    232Displacement

    23315.0

    2343''

    235Compound

    23616.0

    2373''

    238Turbine

    23917.5

    2404''

    241Displacement or Compound

    24425.0

    2454''

    246Turbine

    24730.0

    2486''

    249Displacement or Compound

    25250.0

    2536''

    254Turbine

    25562.5

    2568''

    257Compound

    25880.0

    2598''

    260Turbine

    26190.0

    26210''

    263Compound

    264115.0

    26510''

    266Turbine

    267145.0

    26812''

    269Turbine

    270215.0

    271(c) Where undeveloped land is adjacent to a system or proposed system the Commission may, where appropriate, estimate ERCs for service to future development on the adjacent undeveloped land. Unless the Commission determines that valid local statistical data should be used, ERCs for residential acreage should be estimated as follows:

    321Residential Use

    323ERCs/Acre

    324Mobile home

    3264.8

    327Detached single family

    3304.0

    331Estimates for other types of residential acreage and for commercial and industrial uses shall be made on a case by case basis.

    353Rulemaking Authority 355350.127(2), 356367.121(1)(f) FS. 358Law Implemented 360367.022(6) FS. 362History–New 1-5-84, Formerly 25-10.10, 25-10.010, Amended 11-10-86.

     

Rulemaking Events: