Florida Administrative Code (Last Updated: November 11, 2024) |
25. Public Service Commission |
D25. Departmental |
25-30. Water And Wastewater Utility Rules |
Effective on Monday, November 10, 1986
1Each utility shall inspect and test a representative sample of its meters in service at least once during the intervals set out in this rule.
26Maximum Interval
28Size of Meter
31Between Tests
335/8''
3410 years
363/4''
378 years
391''
406 years
421 1/2''
444 years
462''
474 years
493''
503 years
524''
532 years
556''
561 year
58Rulemaking Authority 60350.127(2), 61367.121 FS. 63Law Implemented 65367.121(1)(a), 66367.122 FS. 68History–New 9-12-74, Formerly 25-10.93, 25-10.093, Amended 11-10-86.